BAMOTOP 281, Frequency signal to current signal converter
- Frequency input, in particular from: BAMOFLU 780, BAMOTUR 781, BAMOMATIC 775, - Input configuration by 3 switches - Ranges: 1 to 25000 Hz - Output: 0/4-20 mA or 0-5/10 V, galvanic insulated - Response time: 5 ms to 10 s - Main power: 85 to 250 V AC - Sensor supply: 12 V DC |
The converter BAMOTOP 281 transforms numerically a frequency signal to transmit an analogic current or voltage. Inputs types are: free voltage contacts, all switches, CMOS, TTL, Hall Effect sensors, NPN/PNP... The output range is configured on site by switches. There are two more configurable parameters: - Minimal response time, to fix the minimal period for signal output actualization; it also filters any over gap or high frequency signals. - Maximal response time, to fix the low frequency limit. The converter BAMOTOP 281 is particularly well adapted for our BAMOFLU, BAMOTUR, BAMOMATIC, FFG, MICRO-STREAM and all counters with pulse signal output with a frequency above 1 Hz.
Main power: 85 to 250 V AC - 48 to 62 Hz - 6.5 VA Sensor supply: 12 V CC ± 25% / 60 mA as a maximum Electrical connections: screw connectors Frequency range: scalable between 1 to 25 kHz Output: 0/4 - 20 mA (maximal 500 Ohm) or 0-5/10 V (minimal 1 kOhm) Accuracy: ± 0.1 % Resolution: 5 μA min. / 3.5 mV min. Response time: adjustable from 5 ms to 10 s Ambient temperature: 0 to 50°C (storage – 40...+80°C)
|
 |
|