| General Information |
|
| General Catalogue |
|
| At a glance |
 |
|
|
| T2FR 5333, PROGRAMMABLE 2 WIRES TRANSMITTER |
General Catalogue 601_1 |
|
Previous Page |
|
|
|
Starting up Notice |
|
|
|
|
|
T2FR 5333

|
|
T2FR 5333, PROGRAMMABLE 2 WIRES TRANSMITTER
- PT100 ohm and resistance input - Programmable by computeur - 4/20mA or 20/4 mA - SI EEx ia IIC, T1 -T6 in option |
Temperature linear measure with resistance sensor, Pt 100, Pt 1000, Ni 100. Resistance conversion to a standard 4-20mA signal (RTM) With ohmic input, it is possible to make a 60 points linearization from customer specification (specially for RTM) To avoid lost or modification of data, in case of power outage, calibration data are saved in a EEPROM. T2F5333 is delivered with configuration required by the final user.
Power supply: non EEx: 8,0 ... 35 V EEx: 8,0 ...28 V Internal consumption: 25 mW ... 0,8 W Probe currant: > 0,2 mA, < 0,4 mA Accuracy: ± 0.3% Power outage: 8 Vdc Response time: from 0.33 to 60 s Temperature factor: < ± 0.01 % EC / °C Linearity error: < 0.1 % EC Power supply effect: < 0.005 % EC / Vdc Line resistance (3 wires): < 0.002 Ohm / Ohm <100°C temperature Factor (RDT): ± 0.01°C / ambiant T° CEM data immunity effect: < ± 0.5 % EC Temp calibration: 24°C ± 4°C Input max difference: 50% of max value Tightness (box/terminal): IP68 / IP00 Wires max section: 1 x 1.5 mm2 Max. line resistance (per wire): 10 Ohm Weight: 50 g EC = Calibrated scale
|
 |
|
PROGRAMMABLE 2 WIRES TRANSMITTER
T2FR 5333 |
General Catalogue
601_1 |
|
|
|