Recherche
MENU Catalog Global Sites
BAMO
INTERNATIONAL
European manufacturer of sensors and instruments for liquids
You are in BAMO EU » General Catalog » Level » VESA
General Catalog 540-05
VESA
VESA
Conductive Multi-Level Limit Switch
VESA


Application example
  • Integrated evaluation electronics
  • 4 relay outputs
  • Monitoring of up to 4 level points or Min/Max control (automatic filling and emptying) with overflow / dry-run protection
  • Switchable energizing / de-energizing delay
  • Switchable response sensitivity
APPLICATION

- Level monitoring
- Level control

DESCRIPTION

The VESA electrode controller operates according to the conductive principle, meaning that the electrical conductivity of the liquids to be monitored is used as an electrical connection between the immersed electrodes in order to detect two or four limit levels.
This conductive limit switch is not suitable for liquids containing oil or grease, or for liquids in which electrically conductive or insulating deposits may form. Measuring range: The VESA electrode controller can be used with liquids whose resistance between electrodes is less than 120 kΩ.
The device can be supplied with up to 5 electrode rods.
(to be ordered separately)

Control:
Two different operating modes can be configured:
- Direct monitoring of up to 4 level points (levels)
- Interval switching (MIN/MAX control) with self-holding using electrodes E2, E3 and the reference electrode, and additionally electrodes E1 and E4 for overflow and dry-run protection.
Metal tanks can be connected to electrode E0 and used as an extended reference electrode.

TECHNICAL FEATURES
Power supply   10...30V DC
Power consumption   ~2W
Ambient temperature   -20…+60°C
Medium temperature   max. 100°C
Connection head   Glass fibre reinforced PBT, IP65 according to EN 60529
Max. operating overpressure   6 bar at 20°C, 1 bar at 100°C, higher pressure on request
Process connection   PP, G2" threaded plug
Electrode rods   Stainless steel 316L, length: min. 45mm, max.
2000mm, also available partially insulated
Measuring circuit   Galvanically isolated, AC voltage <5V / <1mA
Sensitivity   Selectable via DIP switch
Low <10 kΩ >0.1 mS
Medium ~60kΩ ~16μS
High >120kΩ <8μS
Reset hysteresis   approx. 10% of the selected sensitivity value
Sensor input   2…5 rods for up to 4 limit values
Indication   LEDs for relay switching status
Operation   6-position DIP switch for operating mode and sensitivity
General Catalog 540-05
20/03/2026 15:51
Conductive Multi-Level Limit Switch
VESA
Technical & Commercial support's main contacts
Ask a QUOTATION online
BAMO Mesures SAS
22, Rue de la Voie des Bans
Parc d'activités de la Gare
95100 ARGENTEUIL France
Tel : +33 (0)1 30 25 83 21
Fax : +33 (0)1 34 10 16 05
Email : export@bamo.fr
Site : http://www.bamo.eu
Siret : 314 055 864 000 65
TVA Intra : FR 08 314 055 864
APE : 4669 B
Capital : 400 000 €
Designed and hosted by CARIMEDIA since 1998
© 1998-2026 All rights reserved - Disclaimer